Accessory parts and Parts to be procured locally

r Accessory parts
Part name
Q'ty
Installation Manual
Heat insulating pipe
Installation pattern
Installation gauge
Pattern fixing screw
Heat insulator
Washer
Hose band
Flexible hose
Heat insulator A
Heat insulator B
Owner's Manual
<Separate sold parts>
Part name
Q'ty
Standard wired
remote controller
Ceiling panel
r Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4" thick 0.8mm)
Connecting pipe (Gas side)
(12.7mm (diam.), Nominal (diam.) 1/2" thick 0.8mm)
Power supply cord (3 cores)
1.5mm² (H07RN-F or 245 IEC66)
Connecting wire (indoor and outdoor wire)
H07RN-F or 245 IEC66 (1.5mm² or more)
Shape
2
These manual
2
1
——
2
4
M5 × 16L
1
8
1
1
1
1
1
Shape
CODE No.
SET
DATA
SETTING
TEST
UNIT No.
R.C.
No.
H
1
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
FILTER
RESET TEST
SET CL
UNIT
1
Usage
(Be sure to hand over to customers)
For heat insulation of pipe connecting section
For confirmation of ceiling opening and main unit position
For positioning of ceiling position
(united with installation pattern)
For attachment of the installation pattern
For heat insulation of drain connecting section
For hanging-down unit
For connecting drain pipe
For adjusting core-out of drain pipe
For sealing of wire connecting port
For sealing of wire connecting port
(Be sure to hand over to customers)
Usage
Model : RBC-AMT32E
Model : RBC-UM11PG(W)E
Thermal insulation for refrigerant pipe
(10mm or more, thermal insulating foam polyethylene)
Thermal insulation for drain pipe
(10mm or more, foam polyethylene)
Drain pipe (VP25)