Herunterladen Inhalt Inhalt Diese Seite drucken

Toshiba RAV-SM402MUT-E Installations-Handbuch Seite 11

Vorschau ausblenden Andere Handbücher für RAV-SM402MUT-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 64
Installation of indoor unit
• Attach the nut (M10 or W3/8: Procured locally) and washer (Ø34 mm)
to the hanging bolt.
• Put washers at either side of the T-groove on the hanging bracket of
the indoor unit in order to hang the unit.
• Using a spirit level, check that all four sides are horizontal.
(Horizontal positioned within 5 mm)
• Cut off the installation gauge from the installation pattern.
• Using the installation gauge check and adjust clearance between the
indoor unit and the ceiling opening (1) (10 to 42 mm on each side).
Ensure that the unit is level to the ceiling and within a distance of (2)
23 mm to 28 mm below.
The installation gauge has details of how to use printed on it.
NOTE
Install the indoor unit so that the end part of opening does not come into
contact with the drain socket piping.
Level vial (Horizontal: within 5 mm)
Indoor unit
Hanging
metal
10 to 42
mm (1)
Installation gauge
REQUIREMENT
Before installation of the indoor unit, be sure to remove
the transportation cushion inserted between the fan and
the bell mouth. Running the unit without removing the
cushion may damage the fan motor.
Be sure to remove the cushion for transportation
between the fan and the bell mouth.
Installation of remote controller (Sold separately)
For installation of the wired remote controller, follow the Installation Manual supplied with the remote controller.
• Do not expose remote controller to direct sunlight or excessive heat.
• When using a wireless type remote controller check receiver on the indoor unit receives a signal.
• For a wireless type controller, ensure that it is used and mounted with a minimum distance of 1m apart from any other
electrical devices (TV, Stereo, etc) because this may cause interference with the devices.
Indoor unit
Hanging bolt
23 to 28
mm
(2)
Ceiling board
Ceiling board
Hanging bolt
(W3/8 or M10)
(1) M10 washer supplied, all other material
must be procured locally.
(2) To ensure that the unit is mounted safely, the
hanging bolt must be positioned just below
the hanging bracket as shown in the diagram.
(2)
23 to 28
Installation gauge
(1) 10 to
42 mm
Installation of ceiling panel
(Sold separately)
Install the ceiling panel after completion of the installa-
tion of the indoor unit, including all piping and wiring.
Install the ceiling panel as per the supplied Installation
Manual.
Check the installation dimensions of the indoor unit and
the ceiling opening are correct and then install.
REQUIREMENT
Ensure the ceiling panel is mated to the ceiling surface
or the indoor unit.
If the panel and unit are not mated together this may
result in the formation of dew condensation causing a
possible water leak.
First remove the 4 corner caps from the ceiling panel
and fit to the indoor unit.
10
(1)
M10 flat washer
(Accessory)
Nut
(2)
(W3/8 or M10)
M10 flat washer
(Accessory)
Nut
(W3/8 or M10)
mm
English-10