Herunterladen Inhalt Inhalt Diese Seite drucken

Selection Of Installation Place; Installation Space - Toshiba RAV-SM402MUT-E Installations-Handbuch

Vorschau ausblenden Andere Handbücher für RAV-SM402MUT-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 64
2

SELECTION OF INSTALLATION PLACE

• The air conditioner must be installed in a location that can support the weight of the unit effectively.
If the unit is not installed on a foundation that can support its weight effectively, the unit may fall down, resulting
in possible human injury.
• Where required ensure that the units installation is sufficient enough to withstand against an earthquake.
An insufficient installation could result in the unit falling, causing possible human injury.
• Install the air conditioner at a minimum height of 2.5 m from the floor.
Do not insert your hands or others into the unit while the air conditioner is operating.
Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
• If a combustible gas leaks and stays around the unit, a fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the following
conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas
(hot spring). (If the unit should be used in these places, special protective measures are necessary.)
• Place exposed to oil, vapor, oil smoke or corrosive gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)
• Place with poor ventilation.
(Before air ducting work, check whether value of air volume, static pressure and duct resistance are correct or not.)

Installation space

Secure the specified space in the figure for installation and servicing.
Ensure there is sufficient space to install the unit and to perform maintenance work as and when required.
Keep 15mm or more for clearance between top plate of the indoor unit and the ceiling surface.
Installation space
English-5
WARNING
CAUTION
1000 or more
Obstacle
5
1000 or more

Werbung