Herunterladen Inhalt Inhalt Diese Seite drucken

Accessory Parts And Parts To Be Procured Locally - Toshiba MMF-AP0151H Installations-Handbuch

Vorschau ausblenden Andere Handbücher für MMF-AP0151H:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 48

Accessory parts and Parts to be procured locally

H Accessory parts
Attached position
Upper part of main unit
Accessory bag
Lower part of main unit
∗ Quantities in the parentheses are for MMF-AP0361, AP0481 and AP0561 models.
The brackets for fixing to the floor are already mounted to the indoor unit.
<Separate sold parts>
Part name
Q'ty
Standard wired
1
remote controller
H Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4" thick 0.8mm)
MMF-AP0151H, MMF-AP0181H
(9.5mm (diam.), Nominal (diam.) 3/8" thick 0.8mm)
MMF-AP0241H to MMF-AP0561H
Connecting pipe (Gas side)
(12.7mm (diam.), Nominal (diam.) 1/2" thick 0.8mm)
MMF-AP0151H, MMF-AP0181H
(15.9mm (diam.), Nominal (diam.) 5/8" thick 1.0mm)
MMF-AP0241H to MMF-AP0561H
Power supply cord
2
Cable 3-core 2.5mm
, in conformity with Design 60245 IEC57
Part name
Bracket for fixing to wall
Installation Manual
Thermal insulator
Screw bolt
Thermal insulator
Bracket for fixing to floor
Shape
Model
RBC-AMT21E
Q'ty
Shape
1
1
These sheets
2
4 (2)
2
2
Refrigerant piping
• Piping material used for the conventional
Usage
refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more
thickness for Ø6.4, Ø9.5, Ø12.7.
Use copper pipe with 1.0 mm or more
thickness for Ø15.9.
• Flare nut and flare works are also different
from those of the conventional refrigerant.
Take out the flare nut attached to the indoor
unit of the air conditioner, and use it.
1
Stored position
Indoor unit
Base for
transportation
Using 4 (2) screw bolts,
fix to the base.

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis