Herunterladen Inhalt Inhalt Diese Seite drucken

Disconnect Emc Filter Or Ground-To-Phase Varistor, If Needed - ABB ACH580-01 Kurzanleitung Für Die Installation

Frames r0 to r5
Vorschau ausblenden Andere Handbücher für ACH580-01:
Inhaltsverzeichnis

Werbung

Disconnect EMC filter or ground-to-phase varistor, if needed

To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as
follows:
1. Switch off the power from the drive.
2. Open the front cover, if not already opened, see figure
3. R0...R3: To disconnect the internal EMC filter, slide the EMC switch in the
direction shown by the arrow.
R4: To disconnect the internal EMC filter, remove the two EMC screws.
4. R0...R3: To disconnect the ground-to-phase varistor, slide the varistor switch in
the direction shown by the arrow.
R4: To disconnect the ground-to-phase varistor, remove the varistor screw.
R0...R2
4
4
R3
3
4
EN – R0...R4 Quick installation guide 27
B1
on page 165.
3
3
3
3
4
R0-
R4
R5
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
ZH

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis