Herunterladen Inhalt Inhalt Diese Seite drucken

Switch Off The Power And Open The Cover; Check The Compatibility With It (Ungrounded) And Corner-Grounded Tn Systems; Emc Filter; Ground-To-Phase Varistor - ABB ACH580-01 Kurzanleitung Für Die Installation

Frames r0 to r5
Vorschau ausblenden Andere Handbücher für ACH580-01:
Inhaltsverzeichnis

Werbung

Switch off the power and open the cover

See figure
B
on page 315.
2. Switch off the power from the drive.
3. IP21, Remove the module cover: Loosen the retaining screws with a screwdriver
(3a) and lift the cover from the bottom outwards (3b) and then up (3c).
4. IP21, Remove the box cover: Loosen the retaining screws with a screwdriver (4a)
and slide the cover downwards (4b).
5. IP55, Remove the front cover: Loosen the retaining screws with a screwdriver
(4a) and lift the cover from the bottom outwards (4b) and then up (4c).
Check the compatibility with IT (ungrounded) and corner-
grounded TN systems

EMC filter

The internal EMC filter is not suitable for use on an IT (ungrounded) system or on a
corner-grounded TN system. Disconnect the EMC filter before connecting the drive to
the supply network. Check the table on page 176.
WARNING! Do not install the drive with the internal EMC filter connected on an
IT system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system), otherwise the system will be connected to ground potential
through the EMC filter capacitors of the drive. This can cause danger, or damage the
drive.
Do not install the drive with the internal EMC filter connected on a corner-grounded
TN system, otherwise the drive will be damaged.
Note: When the internal EMC filter is disconnected, the drive EMC compatibility is
considerably reduced.

Ground-to-phase varistor

The ground-to-phase varistor is not suitable for use on an IT (ungrounded) system.
Disconnect the ground-to-phase varistor before connecting the drive to the supply
network. Check the table on page 176.
WARNING! Do not install the drive with the ground-to-phase varistor
connected on an IT system (an ungrounded power system or a high-
resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can
be damaged.
EN – R5 Quick installation guide 175
R0-
R4
R5
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
ZH

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis