142 Manually ON / OFF
143 Outside tempera-
en
ture switch,
switch-off value
for occupancy time
144 Outside tempera-
ture switch,
switch-off value
for non-occupancy
time
145 Outside tempera-
ture switch,
switc hing differen-
tial
146 Selection time
switch
Block "Legionella function"
147 Periodicity of le-
gionella function
148 Time for charging
149 Dwelling time at
legionella setpoint
Building Technologies
0
(0 / 1)
........................
.
5.0 °C
(−35.0...+35.0)
...................
−5.0 °C
(−35.0...+35.0)
...................
C
3 °C
(1...20)
...................
C
3
(1...3)
........................
.
1
(0...7)
........................
.
05:00
(00:00...24:00)
........................
.
30 min
(0...360)
min
................
74 319 0618 0 a
0 = relay DEENERGIZED
1 = relay ENERGIZED
Function can be provided only
when operating line 141 = 7
Function can be provided only
°C
when operating line 141 = 1
Function can be provided only
°
when operating line 141 = 1
Function can be provided only
°
when operating line 141 = 1
1 = heating program
2 = s w itching program 2
3 = switching program 3
0 = daily
1...7 = weekly, whereby:
1 = always on Monday
2 = always on Tuesday, etc.
For setpoint of legionella func-
tion, refer to line 30
17.04.2008
64/326