System test
GMC Board Alarm Codes
There is an LED on the GMC board that displays any board
LED using the following table. In the case of more than one
error, the error with the highest priority will be displayed
until it is resolved.
In the case of normal operation, the LED flashes at a
frequency of ½ Hz. In the case of an error, the LED remains
off for 4 seconds, then at a frequency of 1Hz, it flashes a
number of times equal to the error code and than remains
off again for 6 seconds. If the error code has 2 digits, the
second digits.
Fault Code
Description
3
Enter water Temperature Thermistor (EWT)
4
5
Air Thermistor of GMC
6
Loss communication to NUI control
7
NUI control Room Thermistor
8
Unit Capacity Mismatch
9
10
11
Air temperature higher than Stop Heat
12
Air temperature lower than Stop Cool
13
14
Loss of Signal From inverter board
15
Exit water Temperature Thermistor (LWT)
17
Inverter Air Thermistor (TO)
18
G-Tr inverter short circuit protection
20
Compressor position Detection Circuit error
21
Inverter Current Sensor error
22
Heat Exchanger Sensors (TE) / (TS)
23
Discharge Temperature Sensor (TD)
24
Outdoor Fan motor error
26
Other inverter board error
27
Compressor Lock
28
Discharge Temperature error
29
Compressor Breakdown
30
Other inverter board error
31
High Temperature Release
Board position
Fig. 16
Legend:
C Installation terminal strip
12
30AW
Example: error 23: LED off for 4 seconds. 2 flashes at a
frequency of 1Hz. Off for 2 seconds. 3 flashes at a frequency
of 1Hz. Off for 6 seconds. The cycle repeats until the LED
turns off because the problem is resolved or if an error with
higher priority occurs.
(Fig. 16)