there is an output (1ph ~ 230V, 2A max) that can be
programmed using the remote User Comfort Interface
(see the control manual, Installation Menu code 106). The
measured relative humidity is higher than the pre-set value
(Installation Menu code 107).
Note: The following function is only active with the User
Comfort Interface installed.
Units without an integrated pump allow driving an external
one.
Terminal strip pin
Description
Additional external temperature probe
Sanitary Water Request
Maximum Frequency Reduction
Compressor
Water Circulator
3-way valve
1- External Heat Source Request
1- Defrost
2- Ambient Temperature Reached
1- Alarm and Defrost
2- Alarm
Description
Additional external temperature probe
Sanitary Water Request
Maximum Frequency Reduction
Compressor
3-way valve
1- External Heat Source Request
1- Defrost
2- Ambient Temperature Reached
1- Alarm and Defrost
2- Alarm
Note: The maximum total instantaneous current must be less than 3.5A. In the case of loads with higher absorbed current, it is
necessary to drive the loads with relays to be inserted between the power supply of the load itself andreg from the terminal strip.
10
30AW
Alternatively, the output can be programmed to provide an
activation signal for an external heat source (such as a gas
heat source on the water system that is activated, turning
the 30AW unit off, when the external temperature is lower
than the programmed threshold (Installation Menu code
148).
30AWH__X
Signal
23 - 24 Input (NTC 3kΩ @25°C)
Input (contact switch quality
13 - 15
>25mA@12V)
Input (contact switch quality
13 - 14
>25mA@12V)
20 - N
Output 230Vac
10 - 18
Output 230Vac
- N
4 - N
Output 230Vac
9 - 19
Clean Output Contact
21 - 22 Clean Output Contact
30AWH__H
Signal
23 - 24 Input (NTC 3kΩ @25°C)
Input (contact switch quality
13 - 15
>25mA@12V)
Input (contact switch quality
13 - 14
>25mA@12V)
10 - 18
Output 230Vac
- N
4 - N
Output 230Vac
5 - N
Output 230Vac
11 - N
Output 230Vac
33AW-CSI
Limits
Installation
Menu Code
N.A.
126
N.A.
N.A.
N.A.
N.A.
1 ph ~ 230V,
N.A.
2A
1 ph ~ 230V,
N.A.
2A
1 ph ~ 230V,
106 - 107 - 148
2A
5A @ 230V
147
5A @ 230V
108
33AW-CSI
Limits
Installation
Menu Code
N.A.
126
N.A.
N.A.
N.A.
N.A.
1 ph ~ 230V,
N.A.
2A
1 ph ~ 230V,
106 - 107 - 148
2A
1 ph ~ 230V,
147
2A
1 ph ~ 230V,
108
2A