12.3. Test run method

1 Turn on the power to the unit at least 12
hours before the test run.
TEST RUN
2 Press the
(Start this operation from the status of re-
mote controller display turned off.)
A
TEST RUN and current operation mode are dis-
played.
MODE
3 Press the
tivate
mode, then check whether cool
COOL
air is blown out from the unit.
MODE
4 Press the
tivate
mode, then check whether warm
HEAT
air is blown out from the unit.
FAN
5 Press the
fan speed changes.
6 Press the ON/OFF button to stop the test
run.

13. Troubleshooting

13.1. How to handle problems with the test run

Error code list: details
Remote controller
display
E0
E1, E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
F1
F8
A0
A2
A3
A6
A7
A8
EF
U2
U2
U3
U4
U6
UE
UL
F8
P1
P2
P4
P5
P5
P6
P6
P8
20
Downloaded from
www.Manualslib.com
button twice continuously.
7
button to ac-
3,4
2
button to ac-
button and check whether
MELANS display
6831, 6834
Remote controller communication – reception error
6201, 6202
Remote controller board error
6832, 6833
Remote controller communication – transmission error
6831, 6834
Remote controller communication – reception error
6832, 6833
Remote controller communication – transmission error
6740, 6843
Communication between indoor and outdoor units – reception error
6841, 6842
Communication between indoor and outdoor units – transmission error
6840, 6843
Communication between indoor and outdoor units – reception error
6841, 6842
Communication between indoor and outdoor units – transmission error
6844
Indoor/outdoor connection wiring error, indoor unit overload (5 units or more)
6845
Indoor/outdoor connection wiring error (interference, loose)
6846
Excessive time in use
0403
Serial communication error
0403
Serial communication error
4103
Reverse phase, out of phase verification
4115
Faulty input circuit
6600
Duplicated M-NET address setting
6602
M-NET error in PH/W transmission
6603
M-NET bus busy
6606
M-NET communication error with P transmission
6607
M-NET error – no ACK
6608
M-NET error- no response
undefined
Undefined error code
1102
Outlet temperature error
1108
CN23 Short-circuit Connector Unplugged
5104
Open/short in discharge temp thermistor
5105
Open/short in liquid temp or condenser/evaporator temp thermistor
4101
Compressor overcurrent interruption (51C operation)
1302
High pressure error (63H1 operation)
1300
Low pressure error (63L operation)
4115
Power synchronous idle circuit error
5101
Inlet sensor error
5102
Piping sensor error
2503
Drain sensor error
2502
Drain overflow protector operation
2500
Water leak error (PDH only)
1503
Freeze prevention operation
1504
Surge prevention operation
1110
Piping temperature error
manuals search engine
A
Note:
Point the remote controller towards the indoor unit receiver while follow-
ing steps 2 2 2 2 2 to 6 6 6 6 6 .
TEST RUN
It is not possible to run in FAN, DRY or AUTO mode.
ON/OFF
TEMP
FAN
AUTO STOP
5
MODE
VANE
AUTO START
6
CHECK
LOUVER
h
TEST RUN
min
SET
RESET
CLOCK
Error details
Problem location
Remote Controller
Remote Controller
Remote Controller
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
M-NET board
Outdoor unit
Outdoor unit
M-NET board
M-NET board
M-NET board
M-NET board
M-NET board
M-NET board
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit