BTL6-U101-M_ _ _ _ -A/B/Y/Z-S4
Transducer – Rod Style
4

Installation and connection

4.1

Installation guidelines

Non-magnetizable material
Non-magnetizable material
Magnet
Min. Ø D2 = Minimum diameter of the bore (see Tab. 4-1)
1)
Fig. 4-1:
Installation in non-magnetizable material
Magnetizable material
If using magnetizable material, the transducer must be
protected against magnetic interference through suitable
measures (e.g. spacer ring made of non-magnetizable
material, a suitable distance from strong external magnetic
fields).
Magnet
Spacer ring made of non-magnetizable
material
Magnet
Spacer ring made of non-magnetizable
material
1)
Min. Ø D2 = Minimum diameter of the hole (see Tab. 4-1)
Fig. 4-2:
Installation in magnetizable material
Rod diameter
10.2 mm
Tab. 4-1:
Bore diameter if installed in a hydraulic cylinder
8
english
Bore diameter D2
At least 13 mm
4.2

Preparing for installation

Installation note: We recommend using non-
magnetizable material to mount the transducer and
magnet.
Horizontal assembly: For horizontal assembly with
nominal lengths > 500 mm, support the rod and tighten it
at the end if necessary.
Hydraulic cylinder: If installed in a hydraulic cylinder,
ensure that the minimum value for the bore diameter of the
support piston is complied with (see Tab. 4-1).
Mounting hole: The transducer comes with an
M18×1.5 (ISO) or 3/4"-16UNF (SAE) mounting thread.
Depending on the version, a mounting hole must be made
before assembly.
Fig. 4-3:
Mounting hole M18x1.5 per ISO 6149 O-ring 15.4x2.1
Fig. 4-4:
Mounting hole 3/4"-16UNF per SAE J475 O-ring 15.3×2.4
Magnet: Various magnets are available for the BTL6
transducer (see Accessories on page 21).