Herunterladen Inhalt Inhalt Diese Seite drucken

Installation; Flush Mounting; Selecting The Mounting Site - Siemens AR6181-RX Einbau- Und Inbetriebnahmeanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4

Installation

4.1

Flush mounting

4.1.1

Selecting the mounting site

4.1.2
Installation
Siemens Building Technologies
Fire Safety & Security Products
The reader is designed to be wall-mounted on 60 mm flush-mounting boxes. For
surface mounting, the bottom section of the housing can be affixed to the distance
frame supplied.
The reader should not be mounted directly onto conductive materials, such as
metal surfaces, metal frames (reinforcement) or metal-plated surfaces, as these
surfaces will reduce the reader's range. The clearance to such surfaces should
be at least 3 cm.
If the unit has to be mounted onto a metal surface, the distance frame supplied
can be used to maintain the minimum clearance.
The distance between readers of the same design should not be less than
50 cm.
Before final installation, the planned installation site should be checked for
suitability.
You can tell the direction of the distance frame or the bottom section of the
housing from the inscription " TOP
Fig. 1:
Installation direction
The unit should be installed on a surface that is as even as possible.
Slot the connection board into the bottom section of the housing with the
terminals facing downwards. To do this gently push the locating hooks apart with
your fingers.
Connect the cable to the terminal strip in the bottom section of the housing.
See chapter 5.1 Connecting the reader
Plug the top section onto the bottom section of the housing. In doing so, insert
the male connector of the reader electronics cleanly into socket connector X3 on
the terminal board!
Do not mount the unit to the wall before you have checked the set-up works.
Remove the top section of the housing from the bottom section.
Screw the bottom section of the housing incl. the snapped terminal board onto
the base, using 3 x 16 mm self-tapping screws.
". The arrow must point upwards!
TOP
Installation
7
04.2005

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ar6182-rx

Inhaltsverzeichnis