Setting up
5.2.5

Configuration Mode

16
Siemens Building Technologies
Fire Safety & Security Products
The special configuration mode can be reached with the following DIP-settings. In
this position no cards will be read or any card information transmitted.
DIP1, DIP2, DIP3, DIP4 = off or on
DIP5, DIP6 = on
DIP7, DIP8 = off or on
Within configuration mode you may check or change some additional settings or
get information out of the reader with the ASCII minimal protocol.
ASCII minimal protocol
To operate the ASCII minimal protocol the card reader has to be connected to your
PC. Use serial communication line COM1/2, a converter RS485/232 and a
connecting cable. The communication and operation can be done with a terminal
program like i.e. ProComm. The ASCII minimal protocol allows the configuration of
only one reader. No operation within a bus wiring is possible.
Data frame:
Max. telegram length:
Timeout:
Coding:
Protocol frame
1
2
command
address
Command: 1 byte ASCII, see: chap. 5.2.6 Commands
Address: "0", "1", "2" ..."F": bus address of reader for further extension.
"F": to use in existing version, will not be evaluated by the reader.
Response of reader
1
2
command
address
The reader will respond in the shown format, the address has the fixed value "F".
Data:
The response of the reader can be a short acknowledge like OK or NOK
or any more or less long information you ask for.
Receipt: Positive acknowledge:
Negative acknowledge:
9600 baud, 8 Bit, no parity, 1 stop bit
20 byte
3 sec.
ASCII: "0" .... "9"; "a"...."z"; "A" .... "Z"
3 ... n-1
parameter
end character (CR = 0x0D)
3 ... n-1
data
end character (CR = 0x0D)
„OK" i.e.: after parameter is changed
Error message as text information
n
n
04.2005