Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2

Installation

Siemens Building Technologies
Fire Safety & Security Products
The reader is designed to be wall-mounted on 60 mm flush-mounting boxes. For
surface mounting, the bottom section of the housing can be affixed to the distance
frame supplied.
NOTES:
The reader should not be mounted directly onto conductive materials, such as
metal surfaces, metal frames (reinforcement) or metal-plated surfaces, as these
surfaces will reduce the reader's range. The clearance to such surfaces should
be at least 3 cm.
If the unit has to be mounted onto a metal surface, the distance frame supplied
can be used to maintain the minimum clearance.
The distance between readers of the same design should not be less than 50
cm.
Before final installation, the planned installation site should be checked for suit-
ability.
You can tell the direction of the distance frame or the bottom section of the
housing from the inscription "TOP ". The arrow must point upwards!
Fig. 1
Installation direction
TOP
Installation
7
02.2010

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ar6182-ms

Inhaltsverzeichnis