Setting up
5.1.2

RS485 interface

Controller
(with active termination)
5.1.3

Clock / Data interface

5.2

DIP switch settings

12
Siemens Building Technologies
Fire Safety & Security Products
With RS485 data buses, it can be necessary to use terminating resistors. These
checks should be made for each installation. Generally, a terminating resistor is
only required at the end of the bus, i.e. on the last unit. In order to do this, a bridge
needs to be set up between terminals 1 and 2 of terminal X2 (see
To operate the bus, you need a controller with a terminating resistor and active
termination (see Fig. below).
AR 618x-RX
X2
A
B
without terminating resistor
Fig. 9:
Operating a bus with an RS485 interface
The reader connection using the Clock / Data interface has to be done according to
the figure below. The cable length is limited to a maximum of 100 cm.
CLOCK
Reader-
DATA
CLS
Interface
GND / +V
IN1 / IN2
Fig. 10:
Connection using Clock / Data interface
J1
J2
1 2 3 4 5 6 7 8
ON
OFF
S1
X1
Fig. 11:
Switch positions
AR 618x-RX
X2
X7
X5
X2
X3
X4
1 2 3
Fig. 11
).
AR 618x-RX
X2
T/B
R/A
with terminating resistor
CLK
DAT
AR6181-RX
CLS
GND/ +V
IN1 / IN2
04.2005