Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze i500 Montage- Und Einschaltanleitung Seite 67

Vorschau ausblenden Andere Handbücher für i500:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mains current > 16 A: with mains
choke or mains filter, with
dimensioning for rated power. Rsce ≥
120 is to be met.
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150
pF/m
C-core-core/C-core-shield < 150/300
pF/m
Electric strength
Uo/U = 0.6/1.0 kV
U ≥ 600 V
Climate
1K3 (-25 ... +60 °C)
2K3 (-25 ... +70 °C)
3K3 (-10 ... +55 °C)
Site altitude
0 ... 1000 m a.m.s.l.
1000 ... 4000 m a.m.s.l.
Pollution
Degree of pollution 2
Vibration resistance
Transport
2M2 (sine, shock)
Operation
Amplitude 1 mm
Acceleration resistant up to 0.7 g
Amplitude 0.075 mm
Acceleration resistant up to 1 g
Noise emission
Category C1
Category C2
Noise immunity
Meets requirement in compliance with
EN 61000-3-12
RSCE: short-circuit power ratio at the connection point
of the machine/plant to the public network.
≤ 2.5 mm² / AWG 14
≥ 4 mm² / AWG 12
Uo = r.m.s. value external conductor to PE
U = r.m.s. value external conductor/external
conductor
UL
EN 60721-3-1
Storage
EN 60721-3-2
Transport
EN 60721-3-3
Operation
Operation at a switching frequency of 2 or 4 kHz:
above +45°C, reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8 or 16 kHz:
above +40°C, reduce rated output current by 2.5 %/°C
Reduce rated output current by 5 %/1000 m
EN 61800-5-1
EN 60721-3-2
Germanischer Lloyd 5 ... 13.2 Hz
13.2 ... 100 Hz
EN 61800-5-1
10 ... 57 Hz
57 ... 150 Hz
EN 61800-3
Type-dependent, for motor cable lengths see rated
data
EN 61800-3
Technical data
Standards and operating conditions
6
31

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading