3 Prevention of damage
1
2
MiniCODER panel-mounting socket
1
Machine (e.g. spindle)
2
MiniCODER
3
Panel-mounting socket
4
Evaluation electronics
5
Equipotential bonding cable (only in case of extreme interference)
a
Connecting cable with outer screen and three inner screens
b
Inner screens (3×)
c
Outer screen
The MiniCODER is part of a machine or plant. Integrate the equipotential bonding
for the MiniCODER into the overall screening concept.
Lay the signal cables and control cables physically separate from the power
cables. If this configuration is not possible, use screened twisted pair cables
and/or lay the MiniCODER cable in a steel conduit.
Make sure that external protective measures against surge voltages have been
implemented (EN 61000-4-5).
46
Measuring system
3
c
4
b
a
+5 V
Signal
GND
c
PE
5
Lenord + Bauer