Herunterladen Inhalt Inhalt Diese Seite drucken

Fm/Csa Installation Drawing - PR electronics 5350 Anleitung

Vorschau ausblenden Andere Handbücher für 5350:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

FM / CSA Installation Drawing
LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
OR
Class I, Zone 0, IIC
Approved
Terminal 3, 4, 5, 6
Vt or Uo : 5,71 V
It or Io : 8,4 mA
Pt or Po : 12 mW
Ca or Co : 40 uF
La or Lo : 200 mH
Class I, Zone 0, Ex ia IIC, Entity / FISCO
IS, Class I, Division 1, Group A, B, C, D
Barrier type:
T1..T4:
Ta  +85C
T5:
Ta  +70C
T6:
Ta  +60C
Vmax or Ui
Imax or Ii
120 mA
Pi
0.84 W
Ci
Li
See Installation notes.
Revision date:
2015-10-27

FM/CSA Installation drawing

1
2
5350B
Termi-
6
3
nation
5
4
SENSOR
Terminal 1,2
Entity / FISCO
Linear
Trapezoid
Suitable for
barrier
barrier
FISCO
systems
Ta  +75C
Ta  +85C
Ta  +65C
Ta  +60C
Ta  +45C
Ta  +45C
30 V
30 V
17.5 V
300 mA
250 mA
1.3 W
2.0 W
2.0 nF
2.0 nF
2.0 nF
1 H
1 H
1 H
Version /Revision
V4/R0
5350V113-DE
WWW.PRELECTRONICS.COM
1
1
2
5350B
5350B
6
3
6
5
4
5
SENSOR
SENSOR
Suitable for
FISCO
systems
Ta  +85C
Ta  +60C
Ta  +45C
15 V
900 mA
5.32W
2.0 nF
1 H
5350QFC01
V2R0
5350QE01
Unclassified Location
Associated Apparatus
Barrier or
FISCO Supply
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
2
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
3
4
This device must not be
connected to any
associated apparatus
which uses or generates
more than 250 VRMS
Page:
4/15
16

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis