Note
(Re-)calibration of the keypad
When the lid is closed, all keys are (re-)calibrated (< 5 seconds). During (re-)calibration the LED is on and the keys cannot
be operated.
If one of the keys is pressed for more than 10 seconds, the (re-)calibration of this key begins which has a duration of less
than 10 seconds. Release the key for further operation.
Note
HMI timeout
If no key is pressed for 10 minutes, the display switches to show operation view. If Backlight is set to Automatic, display
backlight goes off automatically 30 seconds after the last keypress.
Note
Operation does not require opening of the device. This means that the high degree of protection of IP67 and safety in
hazardous areas are guaranteed at all times.
5.3
Initial startup
The first time the device is powered up, you will be prompted to set the language. The device always starts up showing
Language in English. When the language has been set, you will be prompted to set the date and time.
Before using the flow meter for the first time, essential parameters should be considered. After confirming/changing date and
time you can choose to accept the default values or start the Quick commissioning wizard.
You will be asked if you want to start the Quick commissioning wizard. If you choose Yes (recommended), the Quick
commissioning wizard will start. If you choose No, you accept the default values of the device, and the next HMI view will be
the operation view 1.
Text
Language
Welcome
Set date and time
Quick commissioning
20
Options/description
Set the language: English, Deutsch, Français, Italiano, Español, 汉语
Information about the Quick commissioning wizard
The set date and time (real time clock) is used for all time stamps of logged information
The Quick commissioning wizard comprises the most important parameters/menus for
quick configuration of the flowmeter
SITRANS FS230
A5E38755607-AA, 02/2017