Herunterladen Inhalt Inhalt Diese Seite drucken

Menu: External Heat Source - Daikin RoCon+ HP Betriebsanleitung

Regelung fuer ehsx(b)04p30d / ehsx(b)04p50d / ehsh(b)04p30d / ehsx(b)08p30d / ehsx(b)08p50d / ehsh(b)08p30d / ehsh(b)08p50d
Vorschau ausblenden Andere Handbücher für RoCon+ HP:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 59
7
Parameter settings
7.5.3

Menu: External heat source

[→ Main menu → Settings → Ext. source]
Parameters
Setting range
Min / Max
Config. of ex-
ternal heat
source
No external heat
generator
Backup heater
BUH
DHW + heating
support
Two external heat
generators
Ext. hot water
1 - 40 kW
power
Ext. power
1 - 40 kW
level 1 (*)
Ext. power
1 - 40 kW
level 2 (*)
Equilibrium
function (*)
Aux. heating al-
ways possible
Aux. heating T-biv.
dependent
Equilibrium
-15 °C - +35 °C
Temp
Tab. 7-15 Parameter in menu: "External heat source"
Operating Instructions
34
Description
Setting of whether there is an additional external heat generator for do-
mestic hot water preparation (DHW) and/or heating support (HZU).
The heat pump is the only heat source
Optional heating rod (3N~) installed in the storage tank
An alternative heat generator (e.g. backup heater 1N~) provides domestic
hot water preparation and backup heating
Two external heat generators: Alternative WEZ 1 (e.g. backup heater 1N~)
takes over domestic hot water preparation and alternative WEZ 2 takes
over heating support
Heat output of the electric heater booster for domestic hot water prepara-
tion
Heat output of the electric heater booster for heating support stage 1
See operating instructions for the BUxx heating element.
Heat output of the electric heater booster for heating support stage 2
See operating instructions for the BUxx heating element.
The bivalence function is only relevant to operation of the optional heater
booster due to a backup request (room heating mode).
Operation of the backup heater is always possible.
Backup heater is only released if the temperature set in the [Equilibrium
Temp] parameter is undercut.
Setting influences the effect of the potential-free AUX switching contact
(toggle switch output A) defined in the [AUX switching function] parameter.
Only if [Equilibrium function] parameter = heating up T-bivalence:
Outside temperature as of which the optional heater booster is activated to
support room heating. The bivalence temperature is relevant to operation
of the optional heater booster due to a backup request (room heating
mode). The temperature of the temperature sensor (information value Tem-
perature
) integrated in the heat pump outdoor unit is used for this.
A
Factory
Incre-
Access
setting
ment
BE HF
-
N
E
3 kW
1 kW
N
E
3 kW
1 kW
N
E
3 kW
1 kW
N
E
-
N
E
0 °C
1 °C
N
E
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis