Wiring

3.
3mm
 11
Pipe mounting of the device
4.5

Post-installation check

• Is the sealing which is spray-applied to the casing undamaged?
• Is the device firmly screwed to the mounting plate or the wall?
• Are the housing frame screws closed tightly?
5
Wiring
WARNING
L
Danger! Electric voltage!
The entire connection of the device must take place while the device is de-energized.
The ground connection must be made before all other connections. Danger if protective
ground is disconnected.
Before commissioning the device, make sure that the supply voltage matches the voltage
specifications on the nameplate.
Provide suitable switch or circuit breaker in building installation. This switch must be
provided close to the device (within easy reach) and marked as a circuit breaker.
Provide overload protection (nominal current ≤ 10 A) for power cable.
• Observe the terminal designation inside the device.
• It is permitted to connect a mixture of safety extra low voltage and voltage which
poses a shock hazard to the relays.
34
4.
RIA46
A0010684
Endress+Hauser

Werbung