Herunterladen Inhalt Inhalt Diese Seite drucken

Connections; 1: Connecting Actuators; 2: Connecting Pump And Boiler Controls; 3: Connections For Away Function - Danfoss Link HC Installationsanleitung

Vorschau ausblenden Andere Handbücher für Link HC:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 13
Installation Guide

Connections

Make sure that all connections to the Danfoss Link™ HC are completed, before connecting to a 230 V
power supply .
1: Connecting actuators (24 V)
If NC (normally closed) actuators are installed for ON/OFF regulation, no further actuator output con-
figuration is needed .
1 . Connect actuator wires to an output .

2: Connecting pump and boiler controls

The relays for pump and boiler are potential free contacts and can thus NOT be used as direct power
supply . Max . load is 230 V, 8 (2) A .
1 . Connect wires for pump and boiler controls to their
respective output .

3: Connections for Away Function

The Away Function ensures a set room temperature fixed at 15°C for all Room Thermostats,
but it can be changed with the Danfoss Link™ CC .
1 . Connect an external ON/OFF switch to the termi-
nals for Away Function . When this switch is closed
(ON) the system will override all room thermostat
set points and change it to 15°C .
6
Danfoss Link™ HC
2 . Fix the cable .
2 . Fix the cable .
2 . Fix the cable .
VIFZL15X
© Danfoss
08/2010

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis