Herunterladen Inhalt Inhalt Diese Seite drucken

Endress+Hauser Proline Promag 53 P Ex-Dokumentation Zu Den Betriebsanleitungen Seite 23

Magnetisch-induktives durchflussmessgerät ii2gd
Vorschau ausblenden Andere Handbücher für Proline Promag 53 P:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

XA023D/06/a3/08.04
50094053
FM 6.0
Proline promag 53
II2GD
Ex documentation
for the BA047D and BA048D operating instructions
according to Directive 94/9/EC (ATEX)
Instrument groups
applies to instruments used in underground mining operations, as well as
I
their above ground operations, which can be endangered by mine gas
and/or flammable dusts.
applies to instruments used in the remaining areas which can be
II
endangered by a potentially explosive atmosphere.
Instrument category
Instruments of this category are for use in areas where ignitable
1G
1D
atmospheres caused by a mixture of air and gases, vapours or mists
or by dust/air mixtures, can exist all of the time or for long periods of
(0)
(20)
time or else frequently.
Instruments of this category are for use in areas where ignitable
2G 2D
atmospheres caused by a mixture of air and gases, vapours or mists
(1)
(21)
or by dust/air mixtures, can exist some of the time.
Instruments of this category are for use in areas where ignitable
3G
3D
atmospheres caused by a mixture of air and gases, vapours or mists
or by dust/air mixtures, are not likely to exist. However, if they do
(2)
(22)
occur then in all probability, only seldom or for short periods of time.
(The figures in brackets refer to IEC)
Built according to European norm = E
Explosion protected electrical equipment = Ex
Ex protection labelling in square brackets refers to "Associated electrical equipment"
Type of protection
o
Oil encapsulated
p
Pressurized apparatus
q
Powder filling
d
Flameproof enclosure
e
Increased safety
Explosion groups
Gases and vapours
(examples)
- Ammonia
- Acetone, aircraft fuel, benzene, crude oil,
diesel oil, ethane, ethanoic acid, ether, gaso-
lines, heating oil, hexane, methane, propane
- Ethylene, isoprene, town gas
- Acetylene, carbon disulphide, hydrogen
Temperature class
Maximum surface temperature
450 °C
300 °C
200 °C
135 °C
100 °C
85 °C
as an example: 0
Definition
i
Intrinsic safety (ia, ib)
n
Non-incendive equipment
m
Encapsulation
s
Special protection
Minimum
EN
ignition
IEC
energy [mJ]
--
IIA
0,18
IIA
0,06
IIB
0,02
IIC
EN / IEC
842 °F
T1
572 °F
T2
392 °F
T3
275 °F
T4
212 °F
T5
185 °F
T6
<
II 2G E Ex ia IIC T6