Command #182 READ TOTALIZER INFORMATION
Request:
- None -
Response:
Totalizer Default Value Value,IEEE 754
TotaliterStatus, 8-bit unsigned char
Totalizer ErrorBehaviour, 8-bit unsigned char (ENUM)
Totalizer Time, Date
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #191 Read Current Output Configuration Information
Request:
- None -
Response:
Current Output Loop Current Mode, 8-bit unsigned integer
Current Output Function, 8-bit unsigned integer
Current Output Alarm Reaction, 8-bit unsigned integer
Current Output Fixed Current Level Value,IEEE 754
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
32 Busy
Command #193 Write Current Output Configuration Information
Request:
Current Output Loop Current Mode, 8-bit unsigned integer
Current Output Function, 8-bit unsigned integer
Current Output Alarm Reaction, 8-bit unsigned integer
Current Output Fixed Current Level Value,IEEE 754
Response:
Current Output Loop Current Mode, 8-bit unsigned integer
Current Output Function, 8-bit unsigned integer
Current Output Alarm Reaction, 8-bit unsigned integer
Current Output Fixed Current Level Value,IEEE 754
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
PollingAddressNotZero
InvalidSelection
Command #195 WRITE SV UNIT CODE
Request:
SVUnitCode, 8-bit unsigned char
Response:
SVUnitCode, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #196 WRITE TV UNIT CODE
Request:
TVUnitCode, 8-bit unsigned char
Response:
TVUnitCode, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
90
Thermischer Masse-Durchflussmesser FMT500-IG (Sensyflow iG)
Anhang 2: Diagnose und HART-Kommandos
Command #200 READ SAP_TASKNUMBER, REAL MANUFACTURER
FINAL ASSEMBLY NO. AND CALIBRATION DATE
Request:
- None -
Response:
SAP_TaskNumber
ManufacturerFANumber
CalDate, Date
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #202 WRITE DISPLAY MASK
Request:
Default_Display_Mask, 8-bit unsigned char
Response:
Default_Display_Mask, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #203 READ DISPLAY MASK
Request:
Response:
Default_Display_Mask, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #204 WRITE LANGUAGE
Request:
Language, 8-bit unsigned char
Response:
Language, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy
Command #205 READ LANGUAGE
Request:
Response:
Language, 8-bit unsigned char
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
7 In Write Protect Mode
32 Busy