ABB FMT500-IG Betriebsanleitung Seite 86

Thermischer masse-durchflussmesser
Vorschau ausblenden Andere Handbücher für FMT500-IG:
Inhaltsverzeichnis

Werbung

COMMAND #46 TRIM PRIMARY VARIABLE CURRENT DAC GAIN
Request:
Externally Measured Primary Variable Current Level, IEEE 754, Units of milliam-
peres
Response:
Externally Measured Primary Variable Current Level, IEEE 754, Units of milliam-
peres
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
3 Passed Parameter too Large
4 Passed Parameter too Small
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
9 Not In Proper Current Mode
11 In Multidrop Mode
16 Access Restricted
32 Busy
COMMAND #47 WRITE PRIMARY VARIABLE TRANSFER FUNCTION
Request:
Primary Variable Transfer Function Code, 8-bit unsigned integer
Response:
Primary Variable Transfer Function Code, 8-bit unsigned integer
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
16 Access Restricted
32 Busy
COMMAND #48 READ ADDITIONAL TRANSMITTER STATUS
Request:
- None -
Response:
IG DIAG 1 , 8-bit unsigned char
IG DIAG 2 , 8-bit unsigned char
IG DIAG 3 , 8-bit unsigned char
IG DIAG 4 , 8-bit unsigned char
IG DIAG 5 , 8-bit unsigned char
IG DIAG 6 , 8-bit unsigned char
ExtendedDeviceStatus(refer to Common Table 17 Extended Device Status Infor-
mation) is 0x00
DeviceOperatingMode (refer to Common Table 14, Operating Mode Codes) (is
0x00)
AnalogChannelSaturated
AnalogChannelFixed
Status FLOW TB, 8-bit unsigned integer
Status TEMP TB, 8-bit unsigned integer
Status HEATER, 8-bit unsigned integer
Status CURRENT, 8-bit unsigned integer
Status INPUT1, 8-bit unsigned integer
Status INPUT2, 8-bit unsigned integer
Status OUTPUT1, 8-bit unsigned integer
Status OUTPUT2, 8-bit unsigned integer
Status FLOW AI, 8-bit unsigned integer
Status TEMP AI, 8-bit unsigned integer
Status TOTAL, 8-bit unsigned integer
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Transmitter-Specific Command Error
8 Warning: Update in Progress
16 Access Restricted
32 Busy
86
Thermischer Masse-Durchflussmesser FMT500-IG (Sensyflow iG)
Anhang 2: Diagnose und HART-Kommandos
COMMAND #49 WRITE PRIMARY VARIABLE SENSOR SERIAL NUMBER
Request:
Primary Variable Sensor Serial Number, 24-bit unsigned integer
Response:
Primary Variable Sensor Serial Number, 24-bit unsigned integer
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
16 Access Restricted
32 Busy
Command #53 WRITE DEVICE VARIABLE UNITS
Request:
Device Variable Code, unsigned-8
Device Variable Units Code (refer to Common Tables Specification), ENUM
Response:
Device Variable Code, unsigned-8
Device Variable Units Code (refer to Common Tables Specification), ENUM
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
11 Invalid Device Variable Code
12 Invalid Units Code
16 Access Restricted
32 Busy
Command #54 READ DEVICE VARIABLE INFORMATION
Request:
Device Variable Code, 8-it unsigned integer
Response:
Device Variable Code, unsigned-8
Device Variable Transducer Serial Number, unsigned-24
Device Variable Limits/Minimum Span Units Code(Common Table Spec.), ENUM
Device Variable Upper Transducer Limit, float
Device Variable Lower Transducer Limit, float
Device Variable Damping Value, float
Device Variable Minimum Span, float
Device Variable Classification, ENUM (Common Table 21), ENUM
Device Variable Family (Common Table 20), ENUM
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
16 Access Restricted
32 Busy
Command #55 WRITE DEVICE VARIABLE DAMPING VALUE
Request:
Device Variable Code, 8-it unsigned integer
Device Variable Damping Value, float
Response:
Device Variable Code, 8-it unsigned integer
Device Variable Damping Value, float
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
3 Passed Parameter Too Large
4 Passed Parameter Too Small
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
8 Set To nearest possible Value
16 Access Restricted
32 Busy
42/14-40-DE