Technical data
Technical data
Rated current
Rated short circuit current
Ambient temperature range
Grid topology
AC overvoltage protection
AC input/output
Frequency
AC inputs
Max. output power
Dimensions (height x width x depth)
Weight (without cables)
Housing
Protection class
AC connection
Data communication connection
Service socket
Compliance with standards
1)
2)
1)
1) 2)
1)
Optional
Pre-fabricated cables
38 kA (250 A gG back-up fuse)
TN (universal: TN-C, TN-S and TT grids)
Type 1+2+3 incl. 80 A back-up fuse
fused 3P 50A NH000 (Fronius Symo)
fused 3P 63A NH000 (Fronius Eco)
Open air wall-mounted housing
H07RN-F 5G10mm² (Fronius Symo)
E-YY-O/J 5G16mm² (Fronius Eco)
1) 2)
Patch cable, 2 m, shielded, RJ45,
200 A
-25 - +45 °C
3PN 400/230V
50 Hz/60 Hz
2 - 6 x max. 20 kVA/input,
120 kVA
750 x 700 x 300 mm
38.5 kg
ALU 99.5HH powder coated
IP 54
UV-resistant
1PN 230 V/16 A/30 mA, CEE
EN 61439-2