g) Function G7 "FLORT SETTING"

Use of an additional external temperature sensor (not included,
available as an accessory) that needs to be connected to the
terminals RT1 and RT2 leads to additional options of use by the
room thermostat, e.g. the additional supervision of the fl oor tem-
perature of a fl oor heating.
After activation of the function G7 "FLORT SETTINGS" and the set-
ting of a temperature, the room thermostat monitors both the
internally installed temperature sensor and the external sensor.
Since a fl oor heating reacts very slowly, only a single
fi xed temperature can be set for the external tempera-
ture sensor. It applies for every day and every time.
Heating mode example:
In heating mode, a room temperature of 23.0 °C is set, the hys-
teresis is set to 0.5 °C and the fl oor temperature is set to 20.0 °C.
If the room thermostat measures a room temperature in excess of
23.5 °C OR the fl oor temperature is above 20.5 °C, the connected
consumer is deactivated.
If the room temperature is below 22.5 °C AND the fl oor tempera-
ture below 19.5 °C, the connected consumer is activated and the
symbol "
" appears.
Cooling mode example:
In cooling mode, a room temperature of 25.0 °C is set, the hys-
teresis is set to 0.5 °C and the fl oor temperature is set to 27.0 °C.
If the room thermostat measures a room temperature below of
24.5 °C OR the fl oor temperature is below 26.5 °C, the connected
consumer is deactivated.
If the room temperature is above 25.5 °C AND the fl oor tempera-
ture below 27.5 °C, the connected consumer is activated and the
symbol "
" appears.