Herunterladen Inhalt Inhalt Diese Seite drucken

pyrexx PX-1C Betriebsanleitung Seite 27

Funk-rauchwarnmelder
Vorschau ausblenden Andere Handbücher für PX-1C:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

The use of smoke alarm devices is gov-
erned by DIN 14676.
Minimum equipment
Bedrooms
Children's bedroom
Guest room
Corridors that serve as escape routes
Stairwells of apartment buildings
Optimal equipment
All residential and hobby rooms
Heating and work spaces
Office or workroom
Cellar
Attic
Conditional equipment
In kitchens, smoke alarm devices must
only be installed when false alarms
(e.g., caused by steam) are excluded
Not recommended
Bathrooms are excluded from the in-
stallation of smoke alarm devices due
to the high development of steam
Operating Manual: PX-1C - Smoke Alarm Device with Radio Link
52
Exception: bathrooms with
washing machines and cabinets
4.1 Area to be monitored
Use a device if at least one of the follow-
ing applies:
Monitoring area less than 60 m
,
2
and ceiling height of less than 6 m
Ceiling panels (height lower than 20 cm)
with joists (ceiling surface less than 36 m
Use additional equipment if at least one
of the following applies:
Monitoring area greater than 60 m
Ceiling height greater than 6 m
High partial walls
Separating pieces of furniture
Platform / gallery (area greater than
16 m², at least 2 m long and wide)
Ceiling panels (height greater
than 20 cm) with joists (ceiling
surface more than 36 m
)
2
In rooms with beams (e.g., wooden
beams), the number and arrange-
ment of the devices depends on
the height of the joists and the
surface formed by the beams.
4.2 Requirements for the
monitoring area
When selecting the appropriate monitor-
ing area, observe the following:
)
2
f Position the device centrally on the ceiling
f Position master or shared radio group at
a central location (e.g., in the corridor)
2
f Maintain an approximately equal
distance between the master and
other devices of a radio group
f Maintain an approximately equal
distance between the shared radio
group and other radio groups
f Install additional equipment if required
f Keep a minimum distance of 2 m to
electronic, radio-based devices
(e.g., wireless routers)
f Keep a minimum distance of 3 m to
other radio smoke alarm device
Operating Manual: PX-1C - Smoke Alarm Device with Radio Link
EN
EN
f Keep a minimum distance of 6 m to
a potential fire source
f Keep a minimum distance of 0.5 m to
surrounding walls, furniture and lamps
Rooms with straight ceilings
(slope angle < 20°)
1/2
1/2
0,5
0,5
0,5
Fig. 4
Rooms with straight ceilings
Allowed
Not allowed
Note the following for locations in rooms
with straight ceilings:
f Select the highest mounting point on
the ceilings
f Mount the devices horizontally to
the mounting surface
53

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis