Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Mains connection: Fuses and cable cross−sections
5.4.3
Mains connection: Fuses and cable cross−sections
Installation in accordance with EN 60204−1
Supply conditions
Range
Fuses
Cables
RCCB
Observe all national and regional regulations!
9300
Type
Operation without mains choke/mains filter
EVS9321−xx
EVS9322−xx
EVS9323−xx
EVS9325−xx
Operation with mains choke/mains filter
EVS9321−xx
EVS9322−xx
EVS9323−xx
EVS9324−xx
EVS9325−xx
EVS9326−xx
1)
Universal current−sensitive earth−leakage circuit breaker
2)
For short−time mains interruptions, use circuit breakers with tripping characteristic "C"
166
Description
l
Utilisation category: only gG/gL or gRL
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
l
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
Rated fuse current
Fuse
Circuit−breaker
[A]
6
C6, B6
6
C6, B6
10
25
6
C6, B6
6
C6, B6
10
10
20
32
l
Cable cross−section
Laying system L1, L2, L3, PE
B2
2
[A]
[mm
]
2)
1
2)
1
B10
1.5
B20
4
2)
1
2)
1
B10
1.5
B10
1.5
B16
2.5
B25
˘
1)
FI
C
2
[mm
]
[mA]
1
1
300
1
2.5
1
1
1
300
1
2.5
4
EDKVS9332X DE/EN/FR 8.0