5.8
Type key
MUB-CAV/VAV
5.9

Motor data

The motor data can be found on the motor name plate and in the motor manufacturer's technical documents.
5.10
Sensor-control module for differential pressure and volume PCA1000/6000D2
5.10.1
General
Depending on the operation mode the controller can be used as a sensor or as a regulator for pressure or air volume.
Factory setting of the controller is CAV- constant air volume.
The controller works in accordance with the set values for pressure or air volume. The measured actual value is com-
pared with the set value and the controller adjusts accordingly 0-10V controlled output for the EC motors. The specific
characteristics of the inlet cone size are considered in the k-factor. Factory setting see table 5. More detailed informa-
tion in the operating manual of the controller module (PCA1000/6000D2).
025 315 EC
Bezeichnung
MUB-CAV/VAV 025 315EC
MUB-CAV/VAV 025 355EC
MUB-CAV/VAV 042 400EC
MUB-CAV/VAV 042 450EC
MUB-CAV/VAV 042 450EC-K
MUB-CAV/VAV 042 500EC
MUB-CAV/VAV 062 560EC
MUB-CAV/VAV 062 630EC
MUB-CAV/VAV 100 630EC
MUB-CAV/VAV 100 710EC
Tab 5: K- Faktor
EC: electronically com-
Motor class
mutated
Rotor diameter
Size
Multibox
MUB CAV/VAV
Artikelnr. K-Faktor
37168
100
37169
143
37170
172
37171
238
37485
235
37172
266
37173
418
37174
500
37486
456
37175
550