Siemens SIPART PS2 Installationsanleitung Seite 52

Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Display
Parameter name
1.YFCT
1)
2.YAGL
2)
3.YWAY
4.INIT
5.SCUR
6.SDIR
7.SPRA
8.SPRE
9.TS
10.SFCT
11.SL0
12.SL1
13.SL2
14.SL3
15.SL4
3)
16.SL5
17.SL6
(example)
18.SL7
19.SL8
20.SL9
21.SL10
22.DEBA
23.YA
24.YE
25.YNRM
26.YCLS
5)
5)
6)
6)
1)
1)
If "turn" is selected, you cannot set 33°
2)
2)
Parameter does not appear if 1.YFCT=turn has been selected
3)
3)
Turning points only appear wih selection 10.SFCT = FrEE
4)
Alternatively "no" if initialization has not yet been carried out
Function
Type of actuator
Rated angle of rotation of feedback
Set transmission ratio selector (7) appropriately
(see view of device)
Leverage ratio (stroke range)
must match set leverage ratio on the actuator
Driver pin must be set to the value of the actuator
travel or, if this value is not scaled, to the next
larger scale value.
Initialization
Current range of setpoint
Setpoint direction
Setpoint for start of split range
Setpoint for end of split range
Setpoint ramp
Setpoint function
Equal-percentage 1 : 25
Equal-percentage 1 : 50
Freely adjustable
Setpoint turning point at 0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Dead zone of controller
Start of manipulated variable limiting
End of manipulated variable limiting
To mech. travel
Standardization of
manipulated variable
Tight closing with manipulated variable
Top and bottom
Function of BI 1
Function of BI 2
Function of alarm output
Response threshold of alarm
5)
NC contact means:
NO contact means:
6)
Normal means:
Inverted means:
Parameter values
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
90°
33°
oFF
5 | 10 | 15 | 20
(short lever 33°)
25 | 30 | 35
(short lever 90°)
40 | 50 | 60 | 70 | 90 | 110 | 130
(long lever 90°)
4)
no
/ ##.#
Strt
0 to 20 mA
0 MA
4 to 20 mA
4 MA
rising
riSE
falling
FALL
0.0 to 100.0
0.0 to 100.0
AUto
0 to 400
Lin
Linear
1 : 25
1 : 50
FrEE
0.0 to 100.0
AUto
0.1 to 10.0
0.0 to 100.0
0.0 to 100.0
MPoS
To flow
FLow
no
Without
uP:
Top only
:dW
Bottom only
uP:dW
Rising
Falling
on
-on
bLc1
bLc2
uP
-uP
doW
-doW
StoP
-StP
on
-on
uP
-uP
doW
-doW
StoP
-StP
no
Strt
oCAY
action with opened switch or Low level
action with closed switch or High level
High level without fault
Low level without fault
Factory setting
Unit
WAY
Degrees
33°
mm
oFF
no
mA
4
riSE
0.0
%
100.0
%
0
s
Lin
0.0
28.5
50.0
62.6
71.5
%
78.5
84.1
88.9
93.1
96.7
100.0
%
AUto
0.0
%
100.0
%
MPoS
no
riSE
oFF
oFF
oFF
10.0
%
%
90.0
s
AUto
%
AUto
oCAY
Customer
setting