During the initialization process "RUN1" to "RUN5" appear one after the other in the lower display.
Note
The initialization process can take up to 15 min depending on the actuator.
Initialization is complete when the following display appears:
The upper value shows the total angle of rotation of the actuator (example 93,5 ).
After you have pressed the mode key
To exit Configuration mode press the mode key
displayed. After you have released the mode key, the unit is in manual mode.
If you want to set further parameters, use the leaflet "Operation – a concise overview" or the Manual.
You can start reinitialization from manual or automatic mode at any time.
8

Conformity

The SIPART PS2 positioner without PROFIBUS PA with the associated options is approved as standard for opera-
tion in zone 1 as EEx ib (see EC prototype test certificate PTB 97 ATEX 2155) as well as in zone 2 as Ex n (see
conformity statement TÜV 97 ATEX 1212).
However, the following requirements must be fulfilled for use in zone 2:
Special rating plates must be used for the positioner and the associated options.
These rating plates can be ordered as a complete set (5 plates) with Order No. C73451–A430–D55.
Use in zone 2 must be identified by adhering the corresponding EEx n rating plate over the standard EEx
ib rating plate, thus cancelling the latter.
Warning
!
Since the maximum values of normal operation may be violated in the event of a fault when using
the positioner and its options in zone 2, the EEx n device and its options must never be used again
subsequently in zone 1.
Certification FMRC (Factory Mutual Research Corporation), no. 6D6A0.AX has also been granted.
briefly, the following display appears:
for more than 5 s. After about 5 s, the software version is