3.3
Extension Kit "Rotary Actuator" 6DR4004–8D
The following are included in the delivery of the extension kit "Rotary actuator" (see Fig. 2 for item Nos.):
Item No.
Quantity
Designation
2
1
Coupling wheel
3
1
Driver
4
1
Multiple scale
4.1
8
Scale
4.2
1
Pointer
14
4
Hexagon head screw
15
4
Lock washer
16
1
Fillister head screw
17
1
Washer
18
1
Hexagon socket screw
19
1
Allen key
3.3.1

Assembly Sequence (see Fig. 2)

1.
Place VDI/VDE 3845 mounting console ((9), actuator-specific, scope of supply of actuator manufacturer)
onto rear of positioner and secure using hexagon head screws (14) and lock washers (15).
2.
Adhere pointer (4.2) onto mounting console in the center of the centering hole.
3.
Push coupling wheel (2) onto positioner axis as far as possible, pull back by about 1 mm, and tighten hexagon
socket screw (18) using the supplied Allen key.
4.
Place the driver (3) onto the end of the actuator shaft and secure using Fillister head screw (16) and washer
(17).
5.
Carefully place positioner with mounting console onto the actuator such that the pin of the coupling wheel
engages in the driver.
6.
Align the positioner/mounting console assembly in the center of the actuator and screw tight.
(Screws not included in delivery; they are part of the actuator mounting console!)
7.
Following startup as described in Section 7: Drive actuator to end position and adhere scale (4.1) onto the
coupling wheel (2) according to the direction of rotation or the turning range. The scale is self-adhesive!
4
Option Modules (see Fig. 3, Appendix)
Unscrew housing cover.
Unscrew module cover (1).
HART module (only for devices without PROFIBUS PA): Place the HART module (2) onto the plug
connector; first remove the plug-in jumper (7) from the top connector.
J
module: Insert the J
y
cable (6).
Alarm module: Insert the alarm module (4) into the upper container slot, and connect using the supplied
ribbon cable (5).
Remarks
Mounting on position feedback shaft of SIPART PS2
Mounting on end of actuator shaft
Indication of actuator position, comprising 4.1 and 4.2
Different divisions
Reference point for scale (adhesive label)
DIN 933 – M6 x 12
S6
DIN 84 – M6 x 12
DIN 125 – 6.4
Premounted with coupling wheel
For item 18
module (3) into the lower container slot, and connect using the supplied ribbon
y
C79000–M7474–C156–01