Fig. 3
Detection range Type 6810-21x-101
Detection range Type 6800-xxx-102/104 (standard lens)
For mounting position, refer to the following table.
NOTE
The mounting height must not exceed 1.2 m.
75
Mounting Height/Field of Application
In order to ensure optimum operation of the FM sensors,
refer to the following table.
FM Sensor
Mounting Height
Mounting Posi-
Type
Field of Application tion of Termi-
nal Screws
6810-21x-101
0,8 - 1,2 m
bottom
6800-xxx-102/104
6800-7x-
0,8 - 1,2 m
102M/104M
(stairwell)
top
2,0 - 2,5 m
(room monitoring)
top
6800-xxx-
0,8 - 1,2 m
103M/104M
(stairwell)
bottom
2,0 - 2,5 m
(room monitoring)
bottom
73
GB
Fig. 4
Detection range Type 6800-xxx-102M/103M/104M
(multi-lens). For example, for use in a stairwell.
For mounting position, refer to following tabular overview.
72
76
GB

Technical Data

6810-21x-101
Dusk sensor:
Switch-off delay:
Detection range:
6800-xxx-102 (M)/103M/104(M)
Dusk sensor:
Switch-off delay:
Detection range
- Standard lens:
- Multi-lens:
General
Type of Protection:
Ambient
temperature range:
75
GB
ca. 5°
ca. 5°
ca. 25°
0,2-1,2 m max.
73
GB
approx. 5 to 1000 lux
approx. 80 secs., permanently set
180° horizontal, 12 m frontal
8 m on each side (see Fig. 3)
approx. 5 to 1000 lux
approx. 2 secs. to 32 min.
180° horizontal
12 m frontal
8 m on each side (see Fig. 3)
Dependent on the specific
mounting height (see Fig. 4, 5)
IP 20
0 to + 35 °C
76
74
Fig. 5
Detection range for Type 6800-xxx-102M/103M/104M
(multi-lens) as a function of the mounting height
- 1.2 m height: (10 m frontal and 2.5 m lateral)
- 2.0 m height: (10 m frontal and 4 m lateral)
- 2.5 m height: (15 m frontal and 5 m lateral)
5m 4m 2,5m
2,5m 4m 5m
77

Restriction of the Detection Range

Use of the Masking Strip
The horizontal detection range of your FM Sensor is 180°.
You may wish to restrict the detection range due to special
conditions at the site.
This can be done as follows:
• Cut the masking strip provided to the desired length.
• Affix the masking strip to the area on the front of the lens
of your FM Sensor where detection is to be prevented.