Schuki 2 22.01.2004 15:49 Uhr Seite 22
ELCB fault indication
Neutral and PE conductors reversed
ELCB protection defective
The fault is indicated as portrayed in figure 10.
In this case the ELCB is not tripped, the lamps in the yellow
area continue to glow.
R ~ not permitted
Protective earth resistance too high
Figure 12: All lamps in the yellow area light up. In addition, L3
lights up when the button T is pressed. Simultaneously, the PE
lamp goes out, and L2 flashes on for short period.
L3 goes out after 200 ms; the lamps in the yellow area contin-
ue to glow. The ELCB is not tripped.
The resistance of the PE conductor in unacceptably high. Life
threatening voltages can build up at the earthing contact!
22
Technical data
Operating voltage:
230 V, 50 Hz
Display:
Glow lamps
Nominal fault current:
10-30-100-300-500 mA
200 ms
Permissible ambient
temperature:
-10 °C ... +30 °C
Insertion time:
Unrestricted
Insulation:
Protection class 2
Touch electrode:
Leakage current < 10 µA
Dimensions:
100 x 50 x 75 mm
Weight:
100 g
Fields of application
The tool is intended for use in applications as described in the
operating instructions only.
Any other form of usage is not permitted and can lead to acci-
dents or destruction of the device. Any misuse will result in the
expiry of all guarantee and warranty claims on the part of the
operator against the manufacturer.