4. Design and function
4. Design and function
4.1 Description
Pressures p
and p
1
an elastic diaphragm .
The differential pressure (Δp = p
diaphragm against the measuring range springs .
The deflection, which is proportional to the differential pressure, is transmitted to
the movement in the indicating case via a pressure-tight and low friction rocker
arm .
A magnet , fixed to the rear of the movement, affects the electromagnetic field of
the HALL sensor. The signal that results from this is converted to a standardised
current output signal by the signal conditioning board .
Overpressure safety is provided by metal bolsters resting against the elastic
diaphragm.
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
WIKA operating instructions differential pressure gauge, model DPGT40
act on the media chambers ⊕ and ⊖, which are separated by
2
- p
1
2
⊖
) leads to an axial deflection of the
⊕
EN
11