"Advanced Grid Features": GFDPR - Grid frequency-
dependent power reduction P(F)
GFDPR - Function
GFDPR = Grid Frequency Dependent Power Reduction
description
When the GFDPR function is enabled and the defined grid frequency limit value is exceed-
ed, the effective power is reduced according to a defined gradient.
Once the grid frequency falls within the permitted frequency range again following suc-
cessful power reduction, return to full power takes place depending on the country setup
as follows:
-
-
GFDPR - Applica-
GFDPR ON/OFF = On DisHyst
tion example
On DisHyst
(1)
(2)
P
GFDPR ON DisHyst mode
The inverter increases the power from the current reduced value to the original value
in accordance with the same gradient used for power reduction.
GFDPR ON mode
The inverter will not increase the power to the original value until the frequency is in
the command value range for a specific length of time.
Enable Limit = 50.3 Hz
Derating Gradient = 84 %/Hz
P [%]
P
nom
m
P
red
0
49,6
49,7
49,8 49,9
P
Nominal output
nom
P
Actual power at the moment the
m
limit value is exceeded
P
Reduced power
red
50,0
50,1
50,2
50,3
(1)
(2)
f [Hz]
50,4
50,5
79