Freq dep. Power
Frequency Dependent Power Reduction
Red
(from grid frequency dependent power reduction)
When the GFDPR function is enabled and the specified grid frequency limit value is ex-
ceeded, the effective power is reduced according to a defined gradient.
Selection options
GFDPR On/Off
Activation or deactivation of function
Selection options
Off
On DisHyst
On
Enable Limit
for setting the frequency limit value above which power reduction takes place
Setting range
Unit
Derating Gradient
for setting the gradient at which the effective power is reduced
Setting range
Unit
Reference variable
Frequency Test Time
for setting the waiting time after which the inverter will increase the power again (once the
power has reduced such that the grid frequency is within the permitted frequency range
between Disable Limit Max. and Disable Limit Min.).
Setting range
Unit
Disable Limit Min. / Disable Limit Max.
for setting the upper / lower frequency range limit value
Setting range
Unit
GFDPR On/Off / Enable Limit / Derating Gradient / Frequency
Test Time / Disable Limit Min. / Disable Limit Max. / Alt. Ret.
Grad Thr. / Return Gradient 1 / alt. Return Grad. 1 / Use Return
Grad. 2 / Return Gradient 2 /
Off / On DisHyst / On
Function deactivated
Function activated, no hysteresis
Function activated, with hysteresis
50 - 52
Hz
0.01 - 100
%/Hz
current power at the start of power reduction
0 - 600
s
50 - 52
Hz
65