The chapter "Safety instructions" must be heeded!
6.1 Servicing
● The separator system must be serviced once a year by a
qualified person
1)
Alongside disposal measures, the following jobs must
be carried out:
- Check on the inner walls of the sludge trap and the
grease separator
- Functional check on the electrical devices and installati-
ons, as appropriate.
- Records of the findings and work carried out must be
kept in the operating log and evaluated.
● If present, the electro-mechanical assemblies such as
pumps, valves, shut-off devices etc. must be serviced
according to the manufacturerʼs instructions twice a
year.
6.2 Review (general inspection)
Before initial operation and then at regular intervals of not
longer than 5 years, the separator system must be checked
for proper condition and correct operation by a technical
expert following complete emptying and cleaning.
At least the following points must be checked and recorded:
- Dimensioning of the separator system
- State of repair and airtightness of the separator system
- Condition of the inner walls of the built-in components and
electrical devices, if appropriate

6. Maintenance

- Completeness and plausibility of records in the operating
log
- Proof of correct disposal of the contents of the separator
system removed
- Existence and completeness of the required permits and
documents (approvals, plan sewer system, operating and
servicing instructions)
A test report must be drawn up for the inspection carried
out, listing any faults found. If faults are found, they have to
be eliminated without delay.
The term "qualified" is used to describe employees at the
1)
operators or from third parties who, on account of their
training, knowledge and practical experience, can gua-
rantee that they carry out evaluations or tests in a profes-
sional way in the respective field.
The qualified person can gain the knowledge required for
operating and servicing separator systems at a training
course with subsequent on-site instruction, such as is
offered by respective manufacturers, professional asso-
ciations, chambers of industry and expert organisations
in the field of separator engineering.
Technical experts are the employees of operator-inde-
2)
pendent companies, experts or other institutions who
have certified specialist knowledge about the operation,
servicing and checking of separator systems. In individual
cases, these tests can be carried out in larger company
units by internal experts belonging to the operators who
are independent with regard to their area of responsibility
and not bound by instructions, providing they have the
same qualification and technical equipment available.