Menu 4 Further door settings
Menu
Entry
Selection
item
0
Force detection inactive
1-99
Force detection cycle active, permissible over-
current 101-199 % of the current measured
during the force learning cycle.
The following values can be used
as a guide:
Settings for spring-balanced doors (ap-
prox. 200 kg)
20 – very high sensitivity
25 – high sensitivity (approx. 20 kg)
40 – medium sensitivity
60 – low sensitivity
Settings for heavy spring balanced doors
(approx. 450 kg)
8 – very high sensitivity
9 – high sensitivity (approx. 20 kg)
13 – medium sensitivity
21 – low sensitivity
Settings for heavy springless doors (ap-
prox. 320 kg)
2 – very high sensitivity
5 – high sensitivity (approx. 20 kg)
6 – medium sensitivity
7 – low sensitivity
Settings for heavy springless doors (ap-
prox. 380 kg)
2 – very high sensitivity
6 – high sensitivity (approx. 20 kg)
7 – medium sensitivity
8 – low sensitivity
Default value: 20
49
Motor duty cycle
0
Without limitation (default setting)
1
Geared motor 5.24 (25 min / 35 %)
2
Geared motor 5.24 WS (25 min / 30 %)
3
Geared motor 9.15, 9.20, 9.24 (25 min / 60 %)
4
Geared motor 9.24 WS (25 min / 20 %)
5
Geared motor 6.65 DU (10 min / 35 %)
6
Geared motor 14.15 (25 min / 60 %)
- -
Exit menu
Menu 5 Various settings
Menu
Entry
Selection
item
50
Key switch function (J7)
0
Pulse input OPEN/CLOSE (default setting)
1
Inhibit control panel
2
Inhibit external control elements
3
Inhibit control panel and external control
elements
4
Activate control elements for 10 seconds
5
Switch-over to dead man mode for closing
6
Switch-over to 1/2 opening (winter mode)
7
Pulse input OPEN-STOP-CLOSE
8
Pulse input 1/2 OPEN-STOP-CLOSE
9
Automatic closing AR
10
Pulse input for smoke and heat extraction sys-
tem (setting in menu item 55)
11
Pulse input for smoke and heat extraction sys-
tem, inverted (setting in menu item 55)
12
Mutual locking of door
51
Function of external control devices
0
off (default setting)
1
Dead man open / dead man close
2
Pulse open / dead man close
3
Pulse open / pulse close
4
Pulse 1/2 door opening / pulse close
5
AR operation, automatic closing
6
AR operation, 1/2 door opening
7
Open-close operation
8
Open / close pulse as NO contact
52
001-256 Entry of control address
53
Plug-in module
0
off (default setting)
1, 2, 3, 4 DC module
5
RSE system with OSE
6
RSE system with 8k2
55
Door setting for smoke and heat extraction
system position
58
RSE selection of wicket door contact
Press for 5 s: delete pairing of RSE-system
0
ENS-8200
1
ENS-S 68xx (default setting)
2
NC contact
- -
Exit menu
T100 R-FU 3 kW