Three phases input

MX Frame must be fed from a 3-phase source with neutral.

UPS with common Normal and Bypass AC inputs

Main low-
voltage
switchboard
(MLVS)
Change in SEA between upstream and downstream or galvanic isolation required
Main low-
voltage
switchboard
(MLVS)

UPS with separate Normal and Bypass AC inputs

Main low-
voltage
switchboard
(MLVS)
Change in SEA between upstream and downstream or galvanic isolation required
Main low-
voltage
switchboard
(MLVS)
* The transformer is not necessary if:
Normal and Bypass AC inputs are connected to the same source,
and wires cross sections and wires lengths on Normal and Bypass inputs are identical,
and upstream protection is provided by only one switch with RCD (residual current device) for Normal and Bypass
inputs.
2. Installation
load
load
load
load
34008486EN/AC - Page 21