Herunterladen Inhalt Inhalt Diese Seite drucken

JUMO iTRON 702040 Betriebsanleitung Seite 81

Kompakte mikroprozessorregler b 702040.0 serie
Vorschau ausblenden Andere Handbücher für iTRON 702040:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Input for thermocouple
Designation
Fe-Con
L
Fe-Con
J
Cu-Con
U
Cu-Con
T
NiCr-Ni
K
NiCrSi-NiSi
N
Pt10Rh-Pt
S
Pt13Rh-Pt
R
Pt30Rh-Pt6Rh B
Measurement accuracy: ≤0.4% / 100ppm/°C
Cold junction:
1. These ranges refer to the ambiente temperature of 20°C
Input for standard signals
Designation
Range
Voltage
0 to 10V, R
2 to 10V, R
R
- input resistance
E
4 to 20mA, voltage drop ≤ 3V
Current
0 to 20mA, voltage drop ≤ 3V
Measurement accuracy: ≤0.1% / 100ppm/°C
2.
0 to 1V, R
>10MΩ for Type 702040/41 with 2 relays
E
3.
0.2 to 1V, R
>10MΩ for Type 702040/41 with 2 relays
E
Range
-200 to + 900°C
EN 60584
-200 to +1200°C
-200 to + 600°C
EN 60584
-200 to + 400°C
EN 60584
-200 to +1372°C
EN 60584
-100 to +1300°C
EN 60584
0 to 1768°C
EN 60584
0 to 1768°C
EN 60584
+300 to 1820°C
Pt100 internal
2
> 100kΩ
E
3
> 100kΩ
E
Input for resistance thermometer
1
Designation
Pt100 EN 60751
Pt1000 EN 60751
KTY11-6
Measurement accuracy:
Pt100/1000:
KTY11-6:
Sensor lead
resistance:
Meas. current:
Outputs
Relay:
n.o.(make) contact; 3A at 250V AC resistive load;
150,000 operations at rated load
Logic 0/5V:
Current limiting: 20mA; R
Logic 0/12V:
Current limiting: 20mA; R
Supply
AC 110 to 240V, -15/+10% 48 to 63Hz, or
AC/DC 20 to 30V , 48 to 63Hz (Connect to SELV
or PELV) or
DC 10 to 18V (Connect to SELV or PELV)
Range
-200 to +850°C
-200 to +850°C
-50 to +150°C
≤0.1% / 50ppm/°C
≤1.0% / 50ppm/°C
20Ω max. per lead
250µA
≥250Ω
load
≥600Ω
load
39

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis