INSTALLATION
Power supply
Low voltage, BUS cable and service
X2 Low voltage
Rem.Contr. 3
Remote control
Rem.Contr. 1
Remote control
T(MK)
Mixer circuit temperature sensor and earth (X26)
T(AUSSEN)
Outside temperature sensor and earth (X26)
T(DHW)
DHW cylinder sensor
T(KOLL)
Collector sensor
T(KUE)/T(WW) For solar connection DHW sensor bottom
For cooling flow sensor
T(2. WE)
Temperature sensor heat generator 2
T(Puffer)
Buffer cylinder sensor
X1
Service (CAN BUS)
H
High
L
Low
Ground
+
(only in conjunction with FEK)
X26 GND
BUS connection
Material losses
!
Route BUS cables, power cables and sensor leads sep-
arately.
f Install a J-Y (St) 2 x 2 x 0.8 mm² cable as BUS to the heat
f
pump.
X2
A1
A1
WPM 3 heat pump manager
A2
Operating unit
A3
Heat pump
www.stiebel-eltron.com

12.1 Sensor installation

12.1.1 Contact sensor AVF 6 (included in the pack supplied)

f Connect an additional return sensor in combination with the
f
following heat pump types:
- WPL 13 E/cool
- WPL 10 I
- WPL 10 AC(S)
- WPL 15-25 AC(S) (only in combination with a buffer cylinder)
- WPL 08-22 (S) Trend (only in combination with a buffer
cylinder)
For systems without a buffer cylinder
f Fit the sensor in the heating circuit return as a contact sensor
f
and if necessary, downstream of any overflow valve installed.
For systems with a buffer cylinder
f Fit the sensor as a return temperature sensor in the buffer
f
cylinder.
Installation:
The electrical connection is made at the user interface, specifically
at the "T/Buffer" terminal.
f Clean the pipe.
f
f Apply heat conducting paste.
f
f Secure the sensor with a cable tie.
f
12.1.2 Outside temperature sensor AFS 2 (included in the pack
supplied)
The temperature sensors have a significant influence on the func-
tion of your heating system. Therefore ensure sensors are correctly
positioned and well insulated.
A3
A2
f Install the outside temperature sensor on a north or
f
north-eastern wall. Minimum clearances: 2.5 m above the
ground, and 1 m to the side of windows and doors. The
outside temperature sensor should be freely exposed to the
elements but not placed in direct sunlight.
f Never mount the outside temperature sensor above win-
f
dows, doors or air ducts.
HSBB 3 |
37