3 ELECTRICAL CONNECTIONS
! Risk of injury and material damages due to electric shock !
! Risk of malfunction due to improper installation !
Make the connections by following the indications of the wiring diagram.
WARNING For adequate electrical safety, all cables must have double insulation. Be sure to keep them clearly separated (minimum 4
mm in air or 1 mm through additional insulation) safety extra-low-voltage cables from low-voltage cables (230V ~) by arranging them
within plastic raceways and securing them with appropriate clamps near the terminal blocks.
WARNING For the connection to the network, use multipolar cable of minimum section 3x1,5mm² and the type required by current
regulations. To connect the motors, use cable minimum section 1.5 mm² and the type required by current regulations. By way of example,
if the cable is outside (outdoors), it must be at least equal to H05RN-F while, if inside (in channel), it must be at least equal to H05VV-F.
WARNING Connect to the mains 230 - 240 V ~ 50/60 Hz via an omnipolar switch or other device that ensures omnipolar mains
disconnection, with a contact opening distance = 3 mm.
WARNING All cables should be stripped and unsheathed in the immediate vicinity of the terminals. Keep the cables slightly longer so
that any excess can be removed later.
WARNING Connect the grounding conductor to the appropriate terminal, taking care to keep its length longer than that of the active
conductors so that in the event of the cable coming out of the fixing seat, the active conductors are the first to stretch.
WARNING When connecting the encoder to the control board, use only a dedicated 3x0,22mm² cable.
1
IN 1
INPUT 1 Configurable Input (See P085 for selectable values)
2
C
3
IN 2
INPUT 2 Configurable Input (See P086 for selectable values)
4
C
5
IN 3
INPUT 3 Configurable Input (See P087 for selectable values)
6
C
7
IN 4
INPUT 4 Configurable Input (See P088 for selectable values)
8
C
9
IN 5
INPUT 5 Configurable Input (See P089 for selectable values)
10
C
11
IN 6
INPUT 6 Configurable Input (See P090 for selectable values)
12
C
13
N.O.
OUTPUT 1 Configurable relay output not powered.
14
N.C.
Max contact capacity 2A/250V~ /30V
15
C
16
N.O.
OUTPUT 2 Configurable relay output not powered.
17
N.C.
Max contact capacity 2A/250V~ /30V
18
C
19
N.O.
OUTPUT 3 Configurable relay output not powered.
20
N.C.
Max contact capacity 2A/250V~ /30V
21
C
22
N.O.
OUTPUT 4 Configurable relay output not powered.
23
N.C.
Max contact capacity 2A/250V~ /30V
24
C
25
N.O.
OUTPUT 5 Configurable relay output not powered.
26
N.C.
Max contact capacity 2A/250V~ /30V
27
C
28
N.O.
OUTPUT 6 Configurable relay output not powered.
29
N.C.
Max contact capacity 2A/250V~ /30V
30
C
16
NET-EXP board terminal table
Only resistive loads (See P091 for selectable values)
Only resistive loads (See P092 for selectable values)
Only resistive loads (See P093 for selectable values)
Only resistive loads (See P094 for selectable values)
Only resistive loads (See P095 for selectable values)
Only resistive loads (See P096 for selectable values)