3 Commissioning
32
Min primary value
Display the minimum process value. The process value is accepted at the
• V9H3
beginning of the measurement.
Hint!
Min. process value will be changed to the actual process value on write.
On reset to factory default, the default value is entered.
+10000
Max primary value
Display the maximum process value. The process value is accepted at the
• V9H4
beginning of the measurement.
Hint!
Max. process value will be changed to the actual process value on write.
On reset to factory default, the default value is entered.
-10000
Default values
Entry: 182 (Reset to factory default settings)
• V9H5
0
Output current
Display of the actual output current signal.
• V9H6
Simulation
Entry of simulation mode.
• V9H7
Entry:
Off
Entry of simulation value (current).
Current out (sim)
• V9H8
Entry: 3.58...21.7 mA
Security locking
Release code for setting up.
• V9H9
Entry:
281
Function group: USER INFORMATION
Entry and display of measurement point description (TAG).
Tag number
• VAH0
Entry: 8 characters
-
Descriptor
Entry and display of plant description.
• VAH1
Entry: 16 characters
-
Hardware Version
Display of unit version,
• VAH2
e.g.: 1.0000 indicates version 1.00.00.
Software Version
Display of software version,
• VAH3
e.g.: 8010 indicates version 1.0.
Software Rev.
Serial number
8-digit display of E+H device serial numbers (see legend plates on the
• VAH4
device).
1.
Hint only for Commuwin II operating matrix
2.
not for thermocouples (TC)
iTEMP® HART® Communication
Off
On
Lock = 0
Release = 281
Endress+Hauser