LINETRAXX® SmartDetect RCMS425-L
Anschlussvermögen
starr...........................................................................................0,14 ...1,5 mm²
flexibel, ohne Kunststoffhülse ................................................... 0,25...1,5 mm²
flexibel, mit Kunststoffhülse ..................................................... 0,25...0,5 mm²
Abisolierlänge ....................................................................................................7 mm
Anzugsdrehmoment ..........................................................................0,22...0,25 Nm
Leiterquerschnitt AWG ...................................................................................28...16
Länge der Anschlussleitung für I, Q und M+ ..................................................≤ 10 m
RS-485-Schnittstelle
Leitungslänge (bei 9,6 kbits/s) ...................................................................≤ 1200 m
Empfohlene Leitungen, Schirm einseitig an PE
CAT6/CAT7 ...................................................................................... min. AWG23
min. J-Y(St)Y 2 x 0.6 mm² ..................................................... paarweise verdrillt
NFC-Schnittstelle
Frequenz .................................................................................................... 13,56 MHz
Sendeleistung .......................................................................................................0 W
Digitaleingang I
Externe Beschaltung ...............................................................potentialfreier Kontakt
Digitaler Ein-/Ausgang Q
Low-Pegel (Ausgang) .....................................................................................0...2 V
High-Pegel (Ausgang) ................................................................................ 10 V...U
Multifunktionaler Ausgang M+
Max. Last...........................................................................................................20 mA
Bürde
Stromausgang ........................................................................................≤ 600 Ω
Spannungsausgang ................................................................................≥ 10 kΩ
Schaltglieder (11, 14, 12 / 21, 24, 22)
Relais ........................................................................................................2 Wechsler
Arbeitsweise ................................................Ruhestrom/Arbeitsstrom (Ruhestrom)*
Maximal zulässige Spannung ........................................................AC 380 V / DC 30 V
Schaltvermögen .............................................................................. 1250 VA / 150 W
Mindeststrom ................................................................................10 mA bei DC 10 V
Elektrische Lebensdauer .............................................................. 10000 Schaltspiele
EU-Konformitätserklärung
Bender GmbH & Co. KG erklärt, dass das unter die
Funkrichtlinie fallende Gerät der Richtlinie 2014/53/EU
entspricht. Der vollständige Text der EU-Konformitäts-
erklärung ist über den QR-Code verfügbar:
UKCA-Konformitätserklärung
Bender GmbH & Co. KG erklärt, dass das unter die
Funkrichtlinie fallende Gerät der RED-Richtlinie 2017
(S.I. 2017/1206) entspricht. Der vollständige Text der
UKCA-Konformitätserklärung ist über den QR-Code
verfügbar:
Bender GmbH & Co. KG
Londorfer Straße 65
35305 Grünberg
Germany
Tel.: +49 6401 807-0
info@bender.de
www.bender.de
Connection properties
rigid .......................................................................................... 0.14...1.5 mm²
flexible without plastic ferrule .................................................. 0.25...1.5 mm²
flexible with plastic ferrule ....................................................... 0.25...0.5 mm²
Stripping length .................................................................................................7 mm
Tightening torque ..............................................................................0.22...0.25 Nm
Wire cross-section AWG .................................................................................28...16
Length of the connect. cable for I, Q und M+ .................................................≤ 10 m
RS-485 interface
Cable length (at 9.6 kbits/s)........................................................................≤ 1200 m
Recommended wires, shield on one side to PE
CAT6/CAT7 ...................................................................................... min. AWG23
min. J-Y(St)Y 2 x 0.6 mm² ...............................................................twisted pairs
NFC interface
Frequency .................................................................................................. 13.56 MHz
Transmitting power ..............................................................................................0 W
Digital input I
External circuit ......................................................................... potential-free contact
Digital input/output Q
Low-level (output) ..........................................................................................0...2 V
High-level (output) ..................................................................................... 10 V...U
S
Multifunctional output M+
Max. load ..........................................................................................................20 mA
Burden
current output ........................................................................................≤ 600 Ω
voltage output .......................................................................................≥ 10 kΩ
Switching elements (11, 14, 12 / 21, 24, 22)
Number of switching elements ...............................................2 changeover contacts
Operating mode ................................N/C operation/N/O operation (N/C operation)*
Maximum permissible voltage ......................................................AC 380 V / DC 30 V
Switching capacity .......................................................................... 1250 VA / 150 W
Minimum current ............................................................................10 mA at DC 10 V
Electr. endurance under rated op. conditions ................10000 switching operations
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung nur mit
Genehmigung des Herausgebers.
All rights reserved.
Reprinting and duplicating only with
permission of the publisher.
EU Declaration of Conformity
Bender GmbH & Co. KG declares that the device covered
by the Radio Directive complies with Directive
2014/53/EU. The full text of the EU Declaration of Con-
formity is available via the QR Code:
UKCA Declaration of Conformity
Bender GmbH & Co. KG declares that this device is in
compliance with Radio Equipment Regulations 2017
(S.I. 2017/1206). The full text of the UK Declaration of
Conformity is available via the QR Code:
© Bender GmbH & Co. KG, Germany
Subject to change! The specified
standards take into account the edition
valid until 04/2025 unless otherwise
indicated.
S