Supply the slaves with voltage via the AS-i power supply. Addressing is
carried out via the IR addressing cable E70211.
When the ifm AS-i power supplies SL are used the communication can
be deactivated via a plug on the power supply.
Function check inputs
In case of a fault the high or low activity (NO or NC principle) of the
function check inputs can be set separately for each input via a para-
meter bit. In case of a fault the red LED of the corresponding input
lights and in addition LED 2 (FAULT) flashes.
Parameter
Switch
bit
high-
1
(default)
active
low-
0
active
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED 1 yellow:
• LED green:
• LED 2 red is lit:
• LED 2 red flashing:
• LED 3:
• LED 4 red is lit:
Overload and short circuit of the input supply are signalled to the
AS-i master (version 2.1) via the "peripheral fault" flag in the sta-
tus register.
Fault
FKT LED Fault LED input FKT
input FKT
high
on
low
on
output switched
voltage supply o.k.
AS-i communication error, slave does not
participate in the "normal" data exchange,
e. g. slave address 0
peripheral fault, e.g. sensor supply over
loaded or shorted or fault on the function
check input
infrared receiver
fault - output switched
(function check input)
No error message
on
low
(flashing)
on
high
(flashing)
FKT function check input I1...I4
FKT LED Fault LED
off
off
off
off
PAGE
7