Adjustable parameters

(Menu structure: see fold out page)
C
OUNTER
CM1
0 = counter adding
CM2
1 = counter subtracting
PR
ESET VALUE
PR1
Limit value at which the corresponding output switches
PR2
• Value range: 0 ... 99 999.
R
EPEAT
0 = function not active
1 = function active
- With the counting function subtracting the counter counts
RM1
down to 0. When it has reached the value 0, the output switches
RM2
and the counting operation starts again at PRx (auto-preset).
- With the counting function adding the counters counts up to
the preset value. When it has reached this value, the output
switches and the counting operation starts again at 0 (auto-reset).
P
OWER
0 = function not active
PM1
In the case of power failure the last counter value is deleted.
PM2
1 = function active
In the case of power failure the last counter value is stored.
I
NTEGRATION
IT1
The sensor must detect the object for a minimum time so that the
IT2
corresponding counter counts the pulse.
• Value range: 0 ... 10 000ms.
W
INDOW
WT1
A counting pulse starts a pulse stretching for this range. During this
WT2
time no further pulses are evaluated.
• Value range: 0 ... 10 000ms.
E
D
DGE
0 = The counter counts on the rising edge (i.e. with the changeover:
ED1
sensor receives no light → sensor receives light).
ED2
1 = The counter counts on the falling edge (i.e. with the changeover:
sensor receives light → sensor receives no light).
F
LEETING
The output changes its switching state when the counter value
FT1
(PRx or 0) has been reached for the duration of the set fleeting time.
FT2
Then it returns to the initial state.
• Value range: 0.0 ... 1000.0ms (0.0 = function not active).
M
/ counting function for counter 1/2:
ODE
for counter 1/2:
M
/ repeat function for counter 1/2:
ODE
M
/ last value memory for counter 1/2:
ODE
T
/ minimum pulse length for range 1/2:
IME
T
/ suppression time for range 1/2:
IME
/ edge evaluation for range 1/2:
ETECTION
T
for output 1/2:
IME