Micro Data Center Level A
1
Introduction
EN
This operator manual forms part of the range of
goods supplied. It must be kept near the safe, though
never within the Micro Data Center Level A itself. The
manufacturer reserves the right to make changes to
the data and illustrations in the manual as a result of
technical developments.
Read the operator manual before using the
security safe for the first time.
Republishing, translation and reproduction of this
ocumentation in any form – even of excerpts – require
the written permission of the publisher. This operator
manual is not subject to any amendment service.
The Rittal Micro Data Center Level A represents a ful-
ly climate-controlled, miniature data centre for ensu-
ring functional and data security within networks.
Besides the protection of server and storage applica-
tions, the safe also offers security for decentralised
data backups. Due to its compact size, the Rittal
Micro Data Center Level A can also be integrated in
small offices. It can be used in doctors' surgeries or
lawyers' offices to safeguard personal data, for in-
stance.
The Micro Data Center Level A
offers protection against:
Fire
Burglary
Fire protection
A fire test was successfully conducted over 90 min-
utes on the basis of the standard temperature curve
as defined by the DIN 4102 (EN 1363) standard.
10 minutes within the limits of ΔT < 50 K max. tempe-
rature increase and max. 85% humidity.
Burglary protection
WK 2, resistance to tools comparable
to DIN V EN V 1630
Dust protection
to EN 60 529: IP 55,
protection against ingress of dust
Extinguishing water protection
to EN 60 529: IP 55
2
Product description
The Rittal Micro Data Center Level A is a security safe
that has been tested as a system with a F90 value
and possesses the following standard features:
• Security enclosure, with an operator door and ser-
vice door, and equipped with a three-point locking
system
12
Water
Dust
We reserve the right to further technical modifications of our products. Version 3.0 / 07.2013
• Cable entry in both side elements
• Useful cooling output of 2400 W (L 25/L 25)
• Colour of enclosure and service door: RAL 7035
• Colour of operator door: RAL 9005
• Surface finish: coated sheet steel
• Base/plinth that can be fork-lifted from below,
100 mm high
• Internal dimensions needed for fitting a 19˝ rack:
H x W x D = 800 x 600 x 1000 mm
3
Technische Daten
Micro Data Center Level A
Rittal Micro Data Center Level A
Inner depth 1000 mm, with two doors, 2.4 kW
Art. No.: 7999.999 (with base/plinth)
Weight
Inner effective
with a/c
dimensions
in mm H
x W
i
~ 360 kg
827 x 620 x 1024
19˝ rack for Micro Data Center Level A
H x W x D in mm 800 x 600 x 1000
All weight indications are without interior fittings.
Tab. 1: Technical specifications
4
Safety notes
Danger!
The electrical connection (warning: danger to life!)
and all types of repairs may only be carried out by
technically qualified staff following the manufacturer's
explicit instructions. The mains connection data cited
on the rating plate must be adhered to.
Explosion hazard!
If UPSs with integrated or separate battery packs are
installed in the Micro Data Center Level A, this can
lead to an explosion. UPSs with integrated batteries
or separate battery packs may be installed in the Mo-
dular Safe only with adequate ventilation in ac-
cordance with
EN 50 272-2.
Danger of becoming trapped!
Caution when opening and closing the security
doors – there is a risk of getting caught.
Danger of collapse!
The ground at the site where the Micro Data Center
Level A is to be placed must be able to bear the load
Danger!
The Micro Data Center Level A must never be lifted by
the lug of the climate control unit.
Exterior
dimensions
x D
in mm H
x W
x D
i
i
a
a
a
1699 x 806 x 1319