INSTALLATION
Shutting
down the system
13. Shutting down the system
We recommend running the appliance in fan stage I, even during
prolonged absence.
Property damage
If you interrupt the power supply to the appliance, check
that humidity protection is ensured for the building.
If the appliance needs to be taken out of use for an extended
period, disconnect it from the power supply.
Replacethe filters.
14.
Maintenance
WARNING
Electrocution
Disconnect the appliance from the power supply before
carrying out work inside the appliance.
Isolate the appliance from the power supply.
Activity
Cleaning the condensate
pan
Cleaning the condensate drain
Cleaningthe cross-countercurrent heat exchanger
Cleaning thefans
Cleaningthe preheater
Cleaningthe air ducts
Open the cover beneath the appliance or remove the sus-
pended ceiling panels under the appliance.
Disconnect the appliance from the power supply and secure
it against unauthorised reconnection.
Cleaning the condensate pan
2
1
1 Condensate pan fixing screws
2 Condensate pan
Undo the fixing screws of the condensate pan.
Removethe condensate pan from the appliance carefully as it
may still contain water.
Clean the condensate pan.
www.stiebel-eltron.com
Maintenance
inter-
val (in years)
1
1
3
3
2
3
1
1
Cleaning the condensate drain
Property damage
A blocked condensate drain can cause appliance faults.
Ifthe condensatedrain is blocked, condensatecan escape
from the appliance in an uncontrolled manner and cause
water damage.
Clean the condensate drain at regular intervals.
Cleaning the float module of the condensate pump
This section is not necessary if no condensate pump is connected.
Checkthe functionality of the float module every two years. If
necessary, clean the float module.
You can remove the cover of the float module. During assembly,
ensure that the bevelled side of the float magnet faces upwards.
Push the cover
back onto the float
Cleaning the cross-countercurrent heat exchanger
I Wedge
CAUTIONInjury
After the wedge has been removed, the cross-counter-
current heat exchanger may become detached and fall
down.
When you remove the wedge, you must also remove
the cross-countercurrent heat exchanger.
Removethe wedge from between the appliance body and the
cross-countercurrent heat exchanger.
Carefully remove the heat exchanger from the appliance. Do
not let it fall. Avoid damaging the EPSparts in the appliance.
Use a commercially available vacuum cleaner to remove dust
and other loose dirt particles from the intake and discharge
surfaces.
If required, clean the heat exchanger with warm water
(max. 55 oc) and a commercially available detergent. Do not
use solvents.
Flush the heat exchanger with water.
I-WZ 130 | l-wz 130 Enthalpie
module.
1
I I-WZ 130 E-W | 61